D.3 estándares ul y csa – Yaskawa CIMR-AU 200V Manual del usuario
Página 785

Modelo de
variador
Terminal
Calibre recomendado
AWG, kcmil
Rango de cable
AWG, kcmil
Tamaño de
los
tornillos
Torque de ajuste
N·m (lb.in.)
2A0169
R/L1, S/L2, T/L3
4/0
2/0 a 4/0
M10
18 a 23
(159 a 204)
U/T1, V/T2, W/T3
4/0
3/0 a 4/0
⊖, ⊕1
–
1 a 4/0
⊕3
–
1/0 a 4/0
4
4 a 2
2A0211
R/L1, S/L2, T/L3
1/0 × 2P
1/0 a 2/0
M10
18 a 23
(159 a 204)
U/T1, V/T2, W/T3
1/0 × 2P
1/0 a 2/0
⊖, ⊕1
–
1 a 4/0
⊕3
–
1/0 a 4/0
4
4 a 1/0
2A0250
R/L1, S/L2, T/L3
3/0 × 2P
3/0 a 300
M12
32 a 40
(283 a 354)
U/T1, V/T2, W/T3
3/0 × 2P
3/0 a 300
⊖, ⊕1
–
3/0 a 300
⊕3
–
2 a 300
M10
18 a 23
(159 a 204)
3
3 a 300
M12
32 a 40
(283 a 354)
2A0312
R/L1, S/L2, T/L3
4/0 × 2P
3/0 a 300
M12
32 a 40
(283 a 354)
U/T1, V/T2, W/T3
3/0 × 2P
3/0 a 300
⊖, ⊕1
–
3/0 a 300
⊕3
–
3/0 a 300
M10
18 a 23
(159 a 204)
2
2 a 300
M12
32 a 40
(283 a 354)
2A0360
R/L1, S/L2, T/L3
250 × 2P
4/0 a 600
M12
32 a 40
(283 a 354)
U/T1, V/T2, W/T3
4/0 × 2P
4/0 a 600
⊖, ⊕1
–
250 a 600
⊕3
–
3/0 a 600
M10
18 a 23
(159 a 204)
1
1 a 350
M12
32 a 40
(283 a 354)
2A0415
R/L1, S/L2, T/L3
350 × 2P
250 a 600
M12
32 a 40
(283 a 354)
U/T1, V/T2, W/T3
300 × 2P
300 a 600
⊖, ⊕1
–
300 a 600
⊕3
–
3/0 a 600
M10
18 a 23
(159 a 204)
1
1 a 350
M12
32 a 40
(283 a 354)
<1> Instale un GFCI al usar este calibre de cable, de acuerdo con IEC/EN 61800-5-1.
<2> Instale un GFCI o use un cable de cobre de 10 mm
2
(AWG 8) al usar este calibre de cable, de acuerdo con IEC/EN 61800-5-1.
D.3 Estándares UL y CSA
YASKAWA ELECTRIC SISP C710616 41E Variador de CA YASKAWA A1000 Manual Técnico
785
D
Cumplimiento de estándares